Final | 2/6/2019 | 2/7/2019 | 2/7/2019 | A | PASS |
Eric Strole
|
|
|
Garage Code: 7352 Phone #: ###-#### Inspection requested via web by Dan Otero
|
Rough-in | 11/26/2018 | 11/27/2018 | 11/27/2018 | A | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by Dan Otero
|
Issue PAID IN FULL permit | | | 11/20/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 11/20/2018 | | DONE |
|
|
|
This permit was created on the web by Dan Otero
|