Final | 12/28/2018 | 12/28/2018 | 12/28/2018 | A | PASS |
Brian Scoles
|
|
|
josh ###-####- furnace co ok
|
Final | 12/17/2018 | 12/19/2018 | 12/19/2018 | P | FAIL |
Brian Scoles
|
|
|
Please call client prior to arrival ###-####.
Thank you Phone #: ###-#### Inspection requested via web by Andrea Grigsby- filter box doesnt let filter come out needs to be accessable- single wall flue needs 6" clear to combustibles on furnace flue needs to be ran in b vent- single layer bubble insulation doesnt meet r-6 value and needs to be installed per manufactures installation instruction with air gap
|
Issue PAID IN FULL permit | | | 11/23/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 11/23/2018 | | DONE |
|
|
|
This permit was created on the web by Andrea Grigsby
|