First Notice | 4/19/2019 | 4/19/2019 | 9/17/2019 | | DONE |
Jack Reynolds
|
|
|
This permit finaled on the web by RaChelle Frisbee
|
Final | 4/18/2019 | 4/19/2019 | 4/19/2019 | A | PASS |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by RaChelle Frisbee - final ok card not onsite
|
Card not on site to sign | 4/19/2019 | 4/19/2019 | 4/19/2019 | P | PASS |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by RaChelle Frisbee
|
Final | 4/11/2019 | 4/12/2019 | 4/12/2019 | A | FAIL |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by RaChelle Frisbee - MAU vent needs 1" clearances insulation is touching b vent - one transition on the MAU system and one transition on the fresh air duct needs insulated - line set penetrations need sealed and line set insulation needs UV protection - need to see balance report for exhaust/ MAU system in garage
|
Rough-in | 4/2/2019 | 4/2/2019 | 4/2/2019 | A | PART |
Jack Reynolds
|
|
|
Duct seal inspection. Thank you! Phone #: ###-#### Inspection requested via web by RaChelle Frisbee - duct seal ok on mez only ok for insulation - all exhaust ducts in warehouse need sealed - unit heaters flue pipe need sealed with high temp silicone - one unit heater on the north west needs a sediment trap after shut off valve - MUA unit's flue pipe needs 1" clearances through roof
|
Rough-in | 2/14/2019 | 2/15/2019 | 2/15/2019 | A | FAIL |
Jack Reynolds
|
|
|
Ceiling cover. Thank you Phone #: ###-#### Inspection requested via web by RaChelle Frisbee - duct seal ok - need to see ducts above ceiling insulated before cover of mechanical can be giving
|
Rough-in | 12/18/2018 | 12/19/2018 | 12/19/2018 | A | PART |
Jack Reynolds
|
|
|
Hard lid cover inspection thank you. Phone #: ###-#### Inspection requested via web by RaChelle Frisbee - exhaust fan/ supply runs ok - hard lid cover in bathrooms only ok
|
Issue PAID IN FULL permit | | | 12/3/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 12/3/2018 | | DONE |
|
|
|
This permit was created on the web by RaChelle Frisbee
|