Final | 3/7/2019 | 3/8/2019 | 3/8/2019 | A | PASS |
Brian Scoles
|
|
|
ready for final inspection- stamped approved man j will be onsite and my guys will be there in the AM from 9-11a to meet you. Please call Sam my lead installer when in route Phone #: ###-#### Inspection requested via web by Rick Montgomery- final ok
|
Review - MECHANICAL | 12/26/2018 | 12/26/2018 | 12/26/2018 | | DONE |
Troy James
|
|
|
Manual j report
|
Rough-in | 12/12/2018 | 12/14/2018 | 12/14/2018 | P | PART |
Brian Scoles
|
|
|
PLEASE CALL OUR INSTALL MANAGER TODD 30-45 MINS BEFORE ARRIVAL, SO HE CAN MEET YOU THERE AND ALLOW ACCESS Phone #: ###-#### Inspection requested via web by Rick Montgomery- R/I ok- need to submit manual J to city and get approved- needs fresh air installed to R/A plenum- have issues resolved by final
|
Rough-in | 12/6/2018 | 12/7/2018 | 12/7/2018 | P | FAIL |
Brian Scoles
|
|
|
PLEASE CALL HOMEOWNER TIM WHEN 30-45 MINS IN ROUTE SO HE CAN MEET YOU THERE. THANKS SO MUCH AND HAPPY FRIDAY! Phone #: ###-#### Inspection requested via web by Rick Montgomery- need approved manual J onsite- need to seal all boots to floor with mastic- need to run combustion air from furnace thru roof garage is to small- toe kicks need to be all ducted no wood can be exposed on floor and wood framed in around pipe on floor- register in bath room not completed
|
Issue PAID IN FULL permit | | | 12/6/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 12/6/2018 | | DONE |
|
|
|
This permit was created on the web by Rick Montgomery
|