Final | 1/30/2019 | 1/30/2019 | 1/30/2019 | P | PASS |
Brian Scoles
|
|
|
code 2468 Phone #: ###-#### Inspection requested via web by Randy Hart- final ok
|
Final | 1/29/2019 | 1/29/2019 | 1/29/2019 | A | FAIL |
Jack Reynolds
|
|
|
code 2468 Phone #: ###-#### Inspection requested via web by Randy Hart - need stamped and approved man j onsite
|
Pressure Test | 12/12/2018 | 12/13/2018 | 12/12/2018 | A | CANC |
Brian Scoles
|
|
|
code 2468 Phone #: ###-#### Inspection requested via web by Randy Hart- already completed on 12-12-18
|
Pressure Test | 12/12/2018 | 12/12/2018 | 12/12/2018 | P | PASS |
Brian Scoles
|
|
|
20lb gas pass
|
Rough-in | 12/11/2018 | 12/12/2018 | 12/12/2018 | A | PASS |
Brian Scoles
|
|
|
re rough Code: 2468 Phone #: ###-#### Inspection requested via web by Randy Hart- R/I ok
|
Conference | 12/10/2018 | 12/11/2018 | 12/11/2018 | A | PASS |
Brian Scoles
|
|
|
Witness blast scheduled with Ben @ 1030 am Phone #: ###-#### Inspection requested via web by Randy Hart- duct blast test pass- R/I and gas test still need corrections made
|
Rough-in | 12/7/2018 | 12/10/2018 | 12/10/2018 | P | FAIL |
Brian Scoles
|
|
|
code 2468 Phone #: ###-#### Inspection requested via web by Randy Hart- gauge on gas wont zero out- need to seal exhaust fans to metal 90s on all fans underneath flex- need to seal all boots to floor and seal inside of boots-need to fix all rips and tears in arma flex by final- range duct needs to be smooth walled, remove oval 90 degree and reroute omitting 90 and oval to round reducer- dryer vent needs a termination box installed and seal behind tub so no dry wall will be installed on other side- need to cancel/reschedule duct blast test til after all corrections are made thats on for tomorrow in morning and give one day notice for airbalance test- left correction notice front entry window
|
Pressure Test | 12/7/2018 | 12/10/2018 | 12/10/2018 | P | FAIL |
Brian Scoles
|
|
|
code 2468 Phone #: ###-#### Inspection requested via web by Randy Hart- gauge wont zero out
|
Issue PAID IN FULL permit | | | 12/7/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 12/7/2018 | | DONE |
|
|
|
This permit was created on the web by Randy Hart
|