Permit Information
Permit NumberMEC18-05921
StatusFinaled
Name AIR CARE LLC
Site Address 2466 N MAPLE GROVE RD
Project Name 
Customer NumberR-5081
ePlanReviewNo
Description
Complete HVAC Installation: HVAC
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final2/11/20192/12/20192/12/2019APASS
DetailsChad Schwendiman
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
Final2/7/20192/7/20192/7/2019PFAIL
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN- need to submit manual j with city for approval and have approved manual j onsite for final
Final2/6/20192/6/20192/6/2019PFAIL
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN- equipment installed does not match manual j- need to resubmit to city and have approved manual j onsite for final inspection
Rough-in12/12/201812/13/201812/13/2018APASS
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN- R/I ok
Pressure Test12/13/201812/13/201812/13/2018APASS
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN- 20lb gas pass test whole system ok
Rough-in12/12/201812/12/201812/12/2018PFAIL
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN- insulation shield is not installed now- needs to be 7" round or bigger to maintain 1" clearance to b vent- need to retest gas line since it was rerouted at range to different location
Rough-in12/10/201812/11/201812/11/2018PFAIL
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN- need approved csst nail plates at ceiling both sides at range location- need to seal dryer duct to termination box- insulation shield needs minimum 1" clearance to b vent- left correction notice front entry window
Pressure Test12/10/201812/11/201812/11/2018PPASS
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN- 20lb gas pass
Issue PAID IN FULL permit  12/10/2018 DONE
Payment received via Govolutions
Application received  12/10/2018 DONE
This permit was created on the web by GREGORY ANDERSEN