Final | 3/29/2019 | 4/1/2019 | 4/1/2019 | A | PASS |
Ben Livingston
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
|
Rough-in | 12/27/2018 | 12/28/2018 | 12/28/2018 | A | PASS |
Ben Livingston
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
|
Rough-in | 12/26/2018 | 12/27/2018 | 12/27/2018 | A | FAIL |
Ben Livingston
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN still a fan on 2nd floor not connecte3d please double check all fans on all floors, I also want to see fire dampers before fan covers are installed
|
Rough-in | 12/26/2018 | 12/26/2018 | 12/26/2018 | P | FAIL |
Ben Livingston
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN not all exhaust fans on 2nd floor are connected to exhaust duct
|
Rough-in | 12/21/2018 | 12/24/2018 | 12/24/2018 | P | FAIL |
Ben Livingston
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN BLD still under review, need city stamped plans on site for inspection
|
Rough-in | 12/21/2018 | 12/24/2018 | 12/21/2018 | A | CANC |
Ben Livingston
|
|
|
Greg Phone #: ###-#### Inspection cancelled from web by: GREGORY ANDERSEN
|
Issue PAID IN FULL permit | | | 12/20/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Owner Supplied Equipment | | | 12/20/2018 | | |
|
|
|
|
Application received | | | 12/20/2018 | | DONE |
|
|
|
This permit was created on the web by GREGORY ANDERSEN
|
First Notice | 4/1/2019 | 4/1/2019 | | | |
Ben Livingston
|
|
|
|