Information based on query as of Wednesday, July 3, 2024.
Permit Information
Permit NumberMEC19-00217
StatusFinaled
Name AIR CARE LLC
Site Address 2419 W FAIRVIEW AVE
Project Name 
Customer NumberMF-1101
ePlanReviewNo
Description
New: HVAC **all fixtures and inspecitons for Building A & B under this permit, ref MEC19-04207//leg 9/20/19**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final9/18/20199/19/20199/19/2019APASS
DetailsBen Livingston
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
Final8/27/20198/28/20198/28/2019PPART
DetailsBen Livingston
for TCO Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
- temp C.O.-
Rough-in8/27/20198/27/20198/27/2019PCANC
DetailsBen Livingston
Would like to walk with you today. Call Rob ###-#### Phone #: ###-#### >> Inspection requested via web by GREGORY ANDERSEN Inspection cancelled from web by: GREGORY ANDERSEN
Rough-in8/26/20198/26/20198/26/2019PPART
DetailsBen Livingston
Roof and 1st ; 2nd Floors A ; B Please call Justin when you are on site. Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
- 1st and second floor area a,b, okay-
- need to install firesmoke dampers 2nd and 4th floor electrical room per manufactures instructions fail-
Rough-in8/22/20198/22/20198/22/2019PPASS
DetailsBen Livingston
-A and B 3rd and 4th floor rooms-
Final8/22/20198/22/20198/22/2019PCANC
DetailsBen Livingston
Bldgs A ; B 4th and 3rd floors only Please call Justin when you arrive ###-#### Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
- A,B, 3rd and 4th floor rooms-
CHANGE STATUS TO (ISS)  8/22/2019 DONE
change back to issue status per Ben
Rough-in8/20/20198/21/20198/21/2019APASS
DetailsBen Livingston
c stack units
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
-units C stack 1st to 4th floor--
Rough-in8/20/20198/20/20198/20/2019PFAIL
DetailsBen Livingston
C stack units for final Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
-- armaflex on top of some units need to be finished--
Final8/19/20198/20/20198/20/2019ACANC
DetailsBen Livingston
D stack final please Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
-- rough-in--
Rough-in8/20/20198/20/20198/20/2019PPASS
DetailsBen Livingston
D stack final please Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
-- D stack rooms final only, corridoors still need labels and angle correction on fire smoke damper--
Final8/19/20198/20/20198/19/2019ACANC
DetailsBen Livingston
B Stack Final please Phone #: ###-#### >> Inspection requested via web by GREGORY ANDERSEN Inspection cancelled from web by: GREGORY ANDERSEN
Rough-in8/7/20198/8/20198/8/2019APASS
DetailsBen Livingston
Breezeways Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
Rough-in8/7/20198/7/20198/7/2019PFAIL
DetailsBen Livingston
Breezeways and 4th floor common area Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
-- 4th floor ok--
-- firesmoke damper angles still not to spec--
Rough-in8/6/20198/7/20198/7/2019AFAIL
DetailsBen Livingston
!st floor breezeway''s Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
- firesmoke damper angles no to manufactures instalation instructions-
Rough-in8/6/20198/6/20198/6/2019PPASS
DetailsBen Livingston
D stack range venting Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
-- d 1st to 4th range vent okay, rest of range vents ok to do on room final--
Rough-in8/1/20198/1/20198/1/2019PPASS
DetailsBen Livingston
Cover inspection for 3rd floor common area please Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
-- per conversation with Rob increasing size of return to allow removal of units in ceiling--
Rough-in7/31/20197/31/20197/31/2019APASS
DetailsBen Livingston
D stack trash room Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
-- D 2nd -4th floor trash rooms--
Rough-in7/30/20197/30/20197/30/2019PPASS
DetailsBen Livingston
2nd floor common area Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
Rough-in7/30/20197/30/20197/30/2019ANR
DetailsBen Livingston
2nd floor common area Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
--still working--
Rough-in7/24/20197/25/20197/25/2019APASS
DetailsBen Livingston
Dryer exhaust shaft please Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
-24x24 dryer shaft 2nd to roof duct seal-
Rough-in7/15/20197/15/20197/15/2019PPASS
DetailsBen Livingston
Shaft inspection for B section please Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
-MAU shaft and fire smoke dampers okay, corridor 2nd to 4th floor area B-
Rough-in7/9/20197/9/20197/9/2019PPASS
DetailsBen Livingston
Cover Inspection for corridors 2-4 C stack please Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
C corridors okay fire smoke damper angles 1st to 4th floor area C okay
Rough-in7/1/20197/1/20197/1/2019PPASS
DetailsBen Livingston
Area C shaft 1-4 Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
fire smoke damper clearence 1st to 4th floor okay
Rough-in6/28/20197/1/20197/1/2019APASS
DetailsBen Livingston
1st Floor Cover and C Area Shaft please Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
--1st floor area A cover--
Rough-in6/28/20196/28/20196/28/2019PCANC
DetailsBen Livingston
1st floor A cover. Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
canc. per conversation with Rob
Rough-in6/27/20196/27/20196/27/2019PPASS
DetailsBen Livingston
2nd floor corridor A,C and D excluding fire dampers Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
2nd floor corridor A,C and D, and one fire/smoke damper clearence and angle in corridor
Rough-in6/25/20196/25/20196/25/2019PPASS
DetailsBen Livingston
3rd floor quarters A, C, D, and Shaft for cover please Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
3rd floor hallway A,C,D main duct shaft okay
Rough-in6/11/20196/11/20196/11/2019APASS
DetailsChad Schwendiman
1st floor B grid Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - 117, 119, 120 okay to cover ceilings
Rough-in6/10/20196/10/20196/10/2019PPASS
DetailsBen Livingston
2nd floor A for soffit inspection please Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
2nd floor A soffits
Rough-in6/4/20196/4/20196/4/2019PPASS
DetailsBen Livingston
3rd floor area a soffits okay
Rough-in6/3/20196/4/20196/4/2019ACANC
DetailsBen Livingston
VRF linesets 2nd thru 4th. cover please Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
Rough-in5/28/20195/28/20195/29/2019PPASS
DetailsBen Livingston
VRF linesets 2nd thru 4th. Bathroom next to elevator Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
VRF linesets 2nd thru 4th. 4th floor a soffits
Rough-in5/22/20195/23/20195/23/2019APASS
DetailsBen Livingston
4th floor B soffit cover inspection Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
4th floor B soffit
Rough-in5/22/20195/22/20195/22/2019PPASS
DetailsBen Livingston
3rd floor B soffits Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
3rd floor b soffits
Rough-in5/16/20195/16/20195/16/2019PPASS
DetailsBen Livingston
2nd floor area B please Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
2nd floor area B soffits okay
Rough-in5/15/20195/15/20195/15/2019PPASS
DetailsBen Livingston
Area B 1st floor mechanical shaft duct Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
Area B 1st floor mechanical shaft duct accrossed from kitchen duct seal okay
Rough-in5/8/20195/8/20195/8/2019PPASS
DetailsBen Livingston
Area C 1st floor cover please Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
1st floor C soffits 3 mini split line sets 1st to 4th floor
Rough-in5/7/20195/7/20195/7/2019PPASS
DetailsBen Livingston
3rd floor C Tower for Cover please Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
3rd floor C soffits
Rough-in5/6/20195/6/20195/6/2019PPASS
DetailsBen Livingston
4th floor C Tower for cover please Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
4th floor area C soffits
Rough-in4/28/20194/29/20194/29/2019PPASS
DetailsBen Livingston
1st and 2nd floor A Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
1st 2nd floor area A pre rock
Rough-in4/28/20194/29/20194/29/2019APASS
DetailsBen Livingston
3rd floor A Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
3rd floor area A pre rock okay
Rough-in4/26/20194/26/20194/26/2019PPASS
DetailsBen Livingston
A tower inspection please Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
4th floor area A pre rock
Rough-in4/25/20194/25/20194/25/2019PPASS
DetailsBen Livingston
Cover inspection for Area D 4th floor Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
4th floor area D soffits ok
Rough-in4/18/20194/19/20194/19/2019APASS
DetailsBen Livingston
2nd floor Area C for soffits Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
2nd floor area C soffits okay
Rough-in4/17/20194/17/20194/17/2019PPASS
DetailsBen Livingston
4th floor area B please Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
4th floor area B pre rock okay
Rough-in4/11/20194/12/20194/12/2019APASS
DetailsBen Livingston
3rd floor cover inspection please Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
3rd floor area D soffit okay, 3rd floor area B prerock okay
Rough-in4/9/20194/9/20194/9/2019PPASS
DetailsBen Livingston
Area B 1st ; 2nd floors please Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
1st 2nd floor area B line sets pre rock
Rough-in4/5/20194/5/20194/5/2019PPASS
DetailsBen Livingston
2nd floor Cover please Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
4th floor area c pre rock
2 nd floor area D soffits
Rough-in3/28/20193/29/20193/29/2019APASS
DetailsBen Livingston
1st Floor Soffits please Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
Area D soffit duct okay
Conference3/22/20193/25/20193/25/2019APASS
DetailsBen Livingston
Grease Duct inspection Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
2nd layer fire wrap okay
Rough-in3/22/20193/25/20193/25/2019APASS
DetailsBen Livingston
Area C Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
1st to3rd floor area C line sets okay
Rough-in2/13/20192/14/20192/14/2019APASS
DetailsBen Livingston
Grease exhaust duct wrap and final light test Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
1st layer duct wrap light test okay
Rough-in2/8/20192/11/20192/11/2019APART
DetailsBen Livingston
Light Test for ductwork Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
light test from kitchen to 4th floor pass
final connections at hood and curb remain
Rough-in2/4/20192/5/20192/5/2019APART
DetailsBen Livingston
3rd floor Area D Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
1st to 3rd floor area D pre rock rough-in
Rough-in2/4/20192/4/20192/4/2019PPART
DetailsBen Livingston
4th floor Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
4th floor area D pre rock rough-in
Rough-in1/30/20191/31/20191/31/2019APART
DetailsBen Livingston
Light Test for Grease Duct and Shaft Wall Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
3 16x16 90s pass, shaft wall ok need to see fire smoke damper clearence when installed
Rough-in1/15/20191/16/20191/16/2019APART
DetailsBen Livingston
Light test for future grease duct Contact Rob ###-#### Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
4 8' 16x16 grease duct pass
3 16x16 90 grease duct cannot have flanges on inside fail
Rough-in1/15/20191/15/20191/15/2019PCANC
DetailsBen Livingston
Light test for future grease duct Rob is the contact ###-#### Phone #: ###-#### >> Inspection requested via web by GREGORY ANDERSEN Inspection cancelled from web by: GREGORY ANDERSEN
Issue PAID IN FULL permit  1/15/2019 DONE
Payment received via Govolutions
Application received  1/15/2019 DONE
This permit was created on the web by GREGORY ANDERSEN
First Notice9/19/20199/19/2019   
DetailsBen Livingston