Final | 6/12/2019 | 6/13/2019 | 6/13/2019 | P | PASS |
Ben Livingston
|
|
|
Phone #: ###-#### Inspection requested via web by Arcadio Martinez
|
Rough-in | 2/25/2019 | 2/26/2019 | 2/26/2019 | P | PASS |
Ben Livingston
|
|
|
Phone #: ###-#### Inspection requested via web by Arcadio Martinez
|
Rough-in | 2/22/2019 | 2/25/2019 | 2/25/2019 | P | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Arcadio Martinez- 1) need to seal all register boots to floor 1st floor only 2) still need supply trunk on crawl completed to supply plenum drop and insulated 3) need 1" clearance to b vent at roof and draft stop in chase 2nd floor needs to be completed fully to all sides where no insulation can fall into chase 4) line set needs ran on rough in
left correction notice front window/ no equipment set
|
Rough-in | 2/13/2019 | 2/14/2019 | 2/14/2019 | A | FAIL |
Ben Livingston
|
|
|
Phone #: ###-#### Inspection requested via web by Arcadio Martinez need approved manual j on site for inspection, crawl needs tobe complete
|
Pressure Test | 2/14/2019 | 2/14/2019 | 2/14/2019 | P | PASS |
Ben Livingston
|
|
|
Phone #: ###-#### Inspection requested via web by Arcadio Martinez 20lb 5lb flue
|
Issue PAID IN FULL permit | | | 1/23/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 1/23/2019 | | DONE |
|
|
|
This permit was created on the web by Arcadio Martinez
|