Final | 3/21/2019 | 3/22/2019 | 3/22/2019 | A | PASS |
Chad Schwendiman
|
|
|
re inspection Phone #: ###-#### Inspection requested via web by Randy Hart
|
Final | 3/18/2019 | 3/21/2019 | 3/21/2019 | A | FAIL |
Brian Scoles
|
|
|
Code 2468 Phone #: ###-#### Inspection requested via web by Randy Hart- need uv protection on line set outside at a/c location
|
Conference | 2/13/2019 | 2/15/2019 | 2/15/2019 | A | PASS |
Brian Scoles
|
|
|
confirmed Witness blast scheduled in with Brian @11:30AM Phone #: ###-#### Inspection requested via web by Randy Hart- duct blast test pass
|
Rough-in | 2/6/2019 | 2/7/2019 | 2/7/2019 | P | PASS |
Brian Scoles
|
|
|
re inspection Phone #: ###-#### Inspection requested via web by Randy Hart- R/I ok
|
Rough-in | 2/5/2019 | 2/6/2019 | 2/6/2019 | A | FAIL |
Brian Scoles
|
|
|
code 2468 Phone #: ###-#### Inspection requested via web by Randy Hart- all exhaust fans need sealed from plastic to metal fitting(still ongoing issue)- lineset in attic needs supported every 6 feet- need to insulate fresh air can where ties onto R/A plenum in attic bare metal- left correction notice front window- furnace and coil match man j in attic
|
Pressure Test | 2/5/2019 | 2/6/2019 | 2/6/2019 | A | PASS |
Brian Scoles
|
|
|
code 2468 Phone #: ###-#### Inspection requested via web by Randy Hart- 20lb gas pass- tagged meter location
|
Issue PAID IN FULL permit | | | 2/5/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 2/5/2019 | | DONE |
|
|
|
This permit was created on the web by Randy Hart
|