Print Statement | | | 11/27/2019 | | DONE |
|
|
|
2ND NOTICE
|
Print Statement | | | 11/14/2019 | | DONE |
|
|
|
|
Print Statement | | | 10/24/2019 | | DONE |
|
|
|
|
Print Statement | | | 10/8/2019 | | DONE |
|
|
|
|
Final | 7/11/2019 | 7/12/2019 | 7/12/2019 | A | PASS |
Jack Reynolds
|
|
|
Requesting a Final Inspection for Friday. Please contact Mark ###-#### or Daryl ###-#### before coming out Phone #: ###-#### Inspection requested via web by Heather -Gransbery - final ok - signed occ card
|
Final | 7/10/2019 | 7/11/2019 | 7/11/2019 | A | FAIL |
Jack Reynolds
|
|
|
Requesting a Final Inspection for Thursday. Please contact Mark ###-#### or Daryl ###-#### before coming out Phone #: ###-#### Inspection requested via web by Heather Gransbery - access doors need labeled - line sets need UV protection - condensate lines need installed
|
Rough-in | 6/28/2019 | 7/1/2019 | 7/1/2019 | A | PART |
Jack Reynolds
|
|
|
Requesting an R/I inspection for the Mechanical Room on 7-1-19. Please call Mark before coming out - ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery - duct work in mech room ok - need to see pool heater install instructions for venting - b vent for pool heater needs 1" to combustibles and one location needs clearance reduction installed - mech room needs damper signage installed on wall for final - access doors need installed in ceiling for hvac zones
|
Rough-in | 4/17/2019 | 4/18/2019 | 4/18/2019 | A | PASS |
Jack Reynolds
|
|
|
vent piping rough-in
|
Rough-in | 4/16/2019 | 4/17/2019 | 4/17/2019 | P | FAIL |
Jack Reynolds
|
|
|
Request for inspection on the flue pipe. Please contact Daryl ###-#### with any questions or concerns. Inspection requested via web by Heather Gransbery - south side vent has screw penetrating inner pipe
|
Rough-in | 4/16/2019 | 4/16/2019 | 4/16/2019 | A | FAIL |
Jack Reynolds
|
|
|
-B vent for both pool heaters has screws penetrating inner pipe and needs to be changed out - both vents need an insulation sheild intalled to maintain 1" clearances
|
Rough-in | 3/21/2019 | 3/22/2019 | 3/22/2019 | A | FAIL |
Jack Reynolds
|
|
|
Request for cover R/I inspection. Please contact job lead Daryl with any questions or concerns. ###-#### Inspection requested via web by Heather Gransbery -
|
Rough-in | 3/1/2019 | 3/4/2019 | 3/4/2019 | A | PART |
Jack Reynolds
|
|
|
request for sealer inspection. Please contact job lead Daryl ###-#### with any questions or concerns. Inspection requested via web by Heather Gransbery - duct seal inspection on clubhouse ok for insulation
|
Issue PAID IN FULL permit | | | 2/8/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 2/8/2019 | | DONE |
|
|
|
This permit was created on the web by Heather Gransbery
|