Final | 3/4/2019 | 3/5/2019 | 3/5/2019 | P | PASS |
Jack Reynolds
|
|
|
Hi, The code violations have been redone. Please call 30 mins ahead so we can be there to let you in. ###-#### Brian Phone #: ###-#### Inspection requested via web by Brian Preece - furnace only co ok
|
Final | 2/26/2019 | 3/1/2019 | 3/1/2019 | P | FAIL |
Jack Reynolds
|
|
|
Furnace change-out in basement. This unit was changed out a few weeks ago but, the homeowner will just be in town Friday March 1st. Phone #: ###-#### Inspection requested via web by Brian Preece - furnace single wall flue doesnt have clearnaces to combustibles - gas line needs the shut off valve put before the sediment trap - access door into mech room needs weather stripping put in place to seal mech room from bathroom - homeowner had told me that the water heater was done a few years ago by another contractor and was wondering how it looked. The water heater did have some violations with the shut off valve and sediment trap/ single wall venting being too close to combustilbes/ the vent termination outside being too close to a window and there was no shut off valve in the water line
|
Issue PAID IN FULL permit | | | 2/13/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 2/13/2019 | | DONE |
|
|
|
This permit was created on the web by Brian Preece
|