Card not on site to sign | 3/29/2019 | 3/29/2019 | 3/29/2019 | P | PASS |
Jack Reynolds
|
|
|
|
Final | 3/28/2019 | 3/29/2019 | 3/29/2019 | P | PASS |
Jack Reynolds
|
|
|
Please contact Brian Eddins with any questions at ###-####. Phone #: ###-#### Inspection requested via web by Joshua Bennett - final ok
|
Rough-in | 3/21/2019 | 3/22/2019 | 3/22/2019 | A | PART |
Chad Schwendiman
|
|
|
Please contact Brian Eddins 20 minutes prior to inspection to meet at location. Brian Eddin''s ###-####. Phone #: ###-#### Inspection requested via web by Joshua Bennett - Okay to cover ceilings except for in the conference room, and the area where the VAV is going that serves the coner office
|
Final | 3/14/2019 | 3/15/2019 | 3/15/2019 | A | FAIL |
Jack Reynolds
|
|
|
Please contact Brian Eddins with any HVAC questions at ###-####. Phone #: ###-#### Inspection requested via web by Joshua Bennett - a few location where duct board end caps are falling off and need re installed - west side of building has flex runs that aren't connected to anything - several locations need ducts sealed - couldn't find location of new VAV's
|
Issue PAID IN FULL permit | | | 2/13/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 2/13/2019 | | DONE |
|
|
|
This permit was created on the web by Joshua Bennett
|
First Notice | 3/29/2019 | 3/29/2019 | | | |
Jack Reynolds
|
|
|
|