First Notice | 4/18/2019 | 4/18/2019 | 4/23/2019 | | DONE |
Jack Reynolds
|
|
|
This permit finaled on the web by Brad Knapton
|
Final | 4/18/2019 | 4/18/2019 | 4/18/2019 | P | PASS |
Jack Reynolds
|
|
|
I may not be available till after 4:00pm Phone #: ###-#### Inspection requested via web by Brad Knapton - final ok - signed occ card
|
Rough-in | 3/25/2019 | 3/25/2019 | 3/25/2019 | P | PASS |
Jack Reynolds
|
|
|
Moving fresh air damper to roof Phone #: ###-#### Inspection requested via web by Brad Knapton - R/I ok
|
Conference | 3/4/2019 | 3/5/2019 | 3/5/2019 | P | DONE |
Jack Reynolds
|
|
|
Need to have pre rough-in inspection consultation Phone #: ###-#### Inspection requested via web by Brad Knapton - talked Brad about what needed to be finished for a R/I inspection - need to see condensate lines/rips in lineset fixed/dampers installed in supply branches/ fresh duct needs to be insulated/ access door to FA damper above ceiling - make sure FA is 10' away from any exhaust on the roof or exhaust is 3' above - FA termination cap needs bird screen in place
|
Issue PAID IN FULL permit | | | 2/20/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 2/18/2019 | | DONE |
|
|
|
This permit was created on the web by Brad Knapton
|