Permit Information
Permit NumberMEC19-00738
StatusFinaled
Name A-1 PLUMBING SERVICE INC
Site Address 5208 W FAIRMONT ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration or Repair: Furnace and A/C
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/25/20193/26/20193/26/2019APASS
DetailsJack Reynolds
Please contact Jan at ###-#### prior to arrival. Phone #: ###-#### Inspection requested via web by Andrea Grigsby
- corrections to furnace flue have been made
- final ok
Final3/20/20193/22/20193/22/2019PFAIL
DetailsJack Reynolds
Contact Client Tonya at ###-####

Phone #: ###-#### Inspection requested via web by Andrea Grigsby
- gas line sediment trap ok
- furnace flue fail chimney liner needs to terminate properly out of chimney and have motar gaurd in place then liner/ bvent adapter installed as to be able to run the rest of the flue in double wall per installation specs. flue in unconditoned crawl needs b vent installed through out
Final2/22/20192/27/20192/27/2019PFAIL
DetailsJack Reynolds
Please call ###-#### when you are on your way Phone #: ###-#### Inspection requested via web by Andrea Grigsby
- need to installed sediment trap after shut off valve
- furnace flue in crawl needs to be installed per vent manufactures spec. Chimney liner needs to terminate properly coming out of the chimney. need to also see a chimney liner/ bvent adapter when changing to to b vent in crawl
- need to make sure venting being installed is approved for crawl/ attic
-
Issue PAID IN FULL permit  2/19/2019 DONE
Payment received via Govolutions
Application received  2/19/2019 DONE
This permit was created on the web by Andrea Grigsby