Permit Information
Permit NumberMEC19-00762
StatusFinaled
Name TML LLC
Site Address 2894 S CANONERO WAY
Project Name 
Customer Number22450-23
ePlanReviewNo
Description
Complete HVAC Installation: New HVAC system. Install Fireplace.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final9/6/20199/6/20199/6/2019PPASS
DetailsBrian Scoles
should have passed last inspection
Final8/21/20198/22/20198/22/2019ACANC
DetailsBrian Scoles
garage code #4646 Phone #: ###-#### Inspection requested via web by Debbie Marino- final ok
Final7/19/20197/19/20197/19/2019PFAIL
DetailsBrian Scoles
garage code #4646 Phone #: ###-#### Inspection requested via web by Debbie Marino- still need to seal exterior gas line penetration
Final7/16/20197/16/20197/16/2019PFAIL
DetailsBrian Scoles
garage code #5151 Phone #: ###-#### Inspection requested via web by Debbie Marino- gas line penetration needs sealed at meter location- no access- access pad does not work with 5151 tried multiple times- does this house need a duct blast test completed ???
Pressure Test3/18/20193/19/20193/19/2019APASS
DetailsChad Schwendiman
Phone #: ###-#### Inspection requested via web by Debbie Marino - 20lb gas
Rough-in3/18/20193/19/20193/19/2019APASS
DetailsChad Schwendiman
Phone #: ###-#### Inspection requested via web by Debbie Marino
Pressure Test3/14/20193/15/20193/15/2019AFAIL
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Debbie Marino- gauge below 5 psi on gas gauge
Rough-in3/14/20193/15/20193/15/2019AFAIL
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Debbie Marino- fireplace installation instructions need to be readily accessible they are behind glass- ALL arma flex needs all rips and tears fixed inside wall and attic bare copper showing and supported every 4 feet- gas test fail gauge below 5psi- 2 wire on lineset in attic to close to b vent- need to secure/support b vent in attic- left correction notice front entry window
Rough-in3/13/20193/14/20193/14/2019AFAIL
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Debbie Marino- need approved man j onsite- need installation instructions readily accessable on fireplace- fireplace clearance to fluing combustibles need addressed- all arma flex needs all rips and tears fixed and 2 wire needs clearance to flue piping in attic
Pressure Test3/13/20193/14/20193/14/2019AFAIL
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Debbie Marino- gauge at 5 psi
Issue PAID IN FULL permit  2/20/2019 DONE
Payment received via Govolutions
Application received  2/20/2019 DONE
This permit was created on the web by Debbie Marino