Final | 6/9/2019 | 6/10/2019 | 6/10/2019 | A | PASS |
Brian Scoles
|
|
|
We should be ready to go. My number is above, and Marcus is ###-####. Phone #: ###-#### Inspection requested via web by Nat Golden- final ok
|
Final | 6/6/2019 | 6/6/2019 | 6/6/2019 | P | FAIL |
Brian Scoles
|
|
|
can you call about a 1/2 hour before heading there? Phone #: ###-#### Inspection requested via web by Nat Golden- need installation instruction for fluing off furnace- need to add supply extension and reroute supply duct to leave clear access to furnace in attic and add plywood in front of furnace- need to insulate all bare metal in attic- fresh air can not come from roof- need to run fireplace intake to outside- need to secure all bvent in attic- need combustion air for water heater room- went over with Nat onsite
|
Pressure Test | 3/4/2019 | 3/4/2019 | 3/4/2019 | P | PASS |
Brian Scoles
|
|
|
somebody should be there.can you call a half hour before heading over?
208--###-#### Phone #: ###-#### Inspection requested via web by Nat Golden- 20lb gas pass whole system- tagged gas line
|
Issue PAID IN FULL permit | | | 3/4/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 3/4/2019 | | DONE |
|
|
|
This permit was created on the web by Nat Golden
|
Telephone call | | | 3/4/2019 | | DONE |
|
|
|
called to let know they pulled the wrong type of permit-should ahve been a alteration instead of a complete new home-gave him the info for a refund
|