Final | 5/8/2019 | 5/8/2019 | 5/8/2019 | P | PASS |
Jack Reynolds
|
|
|
final - call brad Phone #: ###-#### Inspection requested via web by Brandon Sorensen - final ok - occ card signed
|
Final | 5/7/2019 | 5/8/2019 | 5/8/2019 | A | FAIL |
Jack Reynolds
|
|
|
final - call mike Phone #: ###-#### Inspection requested via web by Brandon Sorensen - line set penetration needs sealed - line set needs UV protection applied - make up damper has power when exhaust is turned on but doesn't open
|
Rough-in | 4/26/2019 | 4/29/2019 | 4/29/2019 | P | PASS |
Jack Reynolds
|
|
|
cover Phone #: ###-#### Inspection requested via web by Brandon Sorensen - R/I ceiling cover ok. Leave ceiling tile out at furnace so condensate and gas line tie in can be checked
|
Pressure Test | 4/4/2019 | 4/5/2019 | 4/5/2019 | A | PASS |
Jack Reynolds
|
|
|
Flue pressure test and cover - call mike Phone #: ###-#### Inspection requested via web by Brandon Sorensen - 5lb flue pressure test ok
|
Rough-in | 3/29/2019 | 3/29/2019 | 3/29/2019 | P | PASS |
Troy James
|
|
|
Duct seal, cover, flue Phone #: ###-#### Inspection requested via web by Brandon Sorensen Okay to insulate ducts and connect flue. Line set has not been installed
|
Issue PAID IN FULL permit | | | 3/29/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 3/29/2019 | | DONE |
|
|
|
This permit was created on the web by Brandon Sorensen
|