Final | 7/13/2020 | 7/14/2020 | 7/14/2020 | P | PASS |
Jack Reynolds
|
|
|
Gate Code #2390 - Builder ###-#### - HVAC ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks - final ok
|
Final | 7/9/2020 | 7/10/2020 | 7/10/2020 | A | FAIL |
Jack Reynolds
|
|
|
Gate Code #2390 - Builder ###-#### - HVAC ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks - locking caps on all A/C's - gas line penetrations needs sealed - air balance report for system 3 - need installation instructions onsite for unit heater in garage and infrared heaters on patio
|
Final | 6/15/2020 | 6/17/2020 | 6/15/2020 | A | CANC |
Jack Reynolds
|
|
|
Gate Code 2390 Builder ###-#### HVAC ###-#### Phone #: ###-#### >> Inspection requested via web by Arielle Hendricks Inspection cancelled from web by: Arielle Hendricks
|
Pressure Test | 4/14/2020 | 4/14/2020 | 4/14/2020 | P | PASS |
Jack Reynolds
|
|
|
Gate Code #2390 Builder ###-#### HVAC ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks - 20lb underground gas line pressure test ok for clean backfill
|
Mec-Aging Inspection | 1/22/2020 | 1/22/2020 | 1/22/2020 | | DONE |
Jack Reynolds
|
|
|
WIP
|
Mec-Aging Inspection | 10/23/2019 | 10/23/2019 | 10/23/2019 | | DONE |
Jack Reynolds
|
|
|
WIP
|
Rough-in | 7/9/2019 | 7/10/2019 | 7/10/2019 | P | PASS |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by Arielle Hendricks - R/I ok
|
Rough-in | 7/9/2019 | 7/9/2019 | 7/9/2019 | P | FAIL |
Jack Reynolds
|
|
|
Call Brett on your way ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks - need stamped man j onsite - need manual for equipment in wine cellar - line set insulation in wall needs repaired - duct work insulation in crawl needs installed and duct work seams need sealed
|
Pressure Test | 7/9/2019 | 7/9/2019 | 7/9/2019 | P | PASS |
Jack Reynolds
|
|
|
Call Brett on your way ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks - 60lb gas pressure test ok 3- 20lb gas pressure tests ok 3- 5lb flue pressure tests ok - tagged meter location
|
Pressure Test | 7/8/2019 | 7/10/2019 | 7/9/2019 | A | CANC |
Jack Reynolds
|
|
|
Phone #: ###-#### >> Inspection requested via web by Arielle Hendricks Inspection cancelled from web by: Arielle Hendricks
|
Rough-in | 7/8/2019 | 7/10/2019 | 7/9/2019 | A | CANC |
Jack Reynolds
|
|
|
Phone #: ###-#### >> Inspection requested via web by Arielle Hendricks Inspection cancelled from web by: Arielle Hendricks
|
Issue PAID IN FULL permit | | | 3/29/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 3/29/2019 | | DONE |
|
|
|
This permit was created on the web by Arielle Hendricks
|