Print Statement | | | 11/27/2019 | | DONE |
|
|
|
2nd notice
|
Print Statement | | | 11/14/2019 | | DONE |
|
|
|
|
First Notice | 6/6/2019 | 6/6/2019 | 7/23/2019 | | DONE |
Brian Scoles
|
|
|
|
Print Statement | | | 7/23/2019 | | DONE |
|
|
|
|
Final | 6/5/2019 | 6/6/2019 | 6/6/2019 | A | PASS |
Brian Scoles
|
|
|
Rob Phone #: ###-####- final ok- signed occupancy card
|
Rough-in | 5/31/2019 | 5/31/2019 | 5/31/2019 | P | PASS |
Brian Scoles
|
|
|
fire damper inspection- fire damper clearances ok-angles ok- still need all firecaulking removed- Temp occupancy ok- call in final when registers have been installed on fire dampers and fire caulk is removed
|
Conference | 5/30/2019 | 5/31/2019 | 5/31/2019 | A | DONE |
Brian Scoles
|
|
|
Rob Phone #: ###-####- discussed fire dampers and looked at angles- reschedule for R/I in after noon- went over installation instructions with contractor onsite
|
Rough-in | 5/15/2019 | 5/16/2019 | 5/16/2019 | A | FAIL |
Brian Scoles
|
|
|
re-inspect // Rob Phone #: ###-####- need top complete framing around firedampers installed- will need to add return to RTU C5- talked with engineer about issue with return to that RTU- need to submit new plan mod to city for approval and have issued version of print onsite to do inspection next time
|
Rough-in | 5/9/2019 | 5/10/2019 | 5/10/2019 | P | PART |
Brian Scoles
|
|
|
Rob- please call for access Phone #: ###-####- 3 supply fire dampers clearances ok- need to remove all fire caulking- need to run return air per prints and instsll fire dampers or get engineer approval of system installed- seal on exhaust duct ok- ok to cover
|
Final | 5/7/2019 | 5/7/2019 | 5/7/2019 | P | NR |
Chad Schwendiman
|
|
|
Rob Phone #: ###-####
|
Rough-in | 5/7/2019 | 5/7/2019 | 5/7/2019 | P | FAIL |
Chad Schwendiman
|
|
|
Rob Phone #: ###-#### - Need to seal exhaust duct. need access to roof, Need to install sleeves ob fire dampers that comply with the manufactures instructions, Need to install retaining angles per instructions on fire dampers after sheetrock is complete. need to install duct mounted access doors for fire dampers.
|
Issue PAID IN FULL permit | | | 4/19/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 4/19/2019 | | DONE |
|
|
|
This permit was created on the web by Rob Gamache
|