First Notice | 4/3/2020 | 4/3/2020 | 4/3/2020 | | DONE |
Brian Scoles
|
|
|
This permit finaled on the web by Stacia Haumann
|
Final | 4/3/2020 | 4/3/2020 | 4/3/2020 | A | PASS |
Brian Scoles
|
|
|
final ok
|
Final | 3/25/2020 | 3/26/2020 | 3/26/2020 | A | PART |
Brian Scoles
|
|
|
if questions call Noe @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann- need heat trace and insulation installed on condensate drains from cooler/freezer- water heater gas piping and gas piping to RTUs ok- dishwasher gas omitted- will final this permit out when HVAC contrator calls in his inspection- Temp occupancy ok
|
Mec-Aging Inspection | 2/26/2020 | 2/26/2020 | 2/26/2020 | | CANC |
Brian Scoles
|
|
|
needs final called- WIP
|
Rough-in | 11/27/2019 | 12/2/2019 | 12/2/2019 | A | CANC |
Brian Scoles
|
|
|
if questions call Noe @ ###-#### Phone #: ###-#### Inspection requested via web by Stacia Haumann- this was completed on 11-27-19 as a pressure test- talked with Noe to verify no inspection needed- pressure test passed walls ok to cover
|
Pressure Test | 11/27/2019 | 11/27/2019 | 11/27/2019 | P | PASS |
Brian Scoles
|
|
|
20lb gas pass to dishwasher- ok to cover walls
|
Pressure Test | 11/8/2019 | 11/8/2019 | 11/8/2019 | P | PASS |
Brian Scoles
|
|
|
Noe- ###-####- 60lb gas pass whole systen to regulator shutoff valves roof and kitchen and water heaters- tagged meter location
|
Rough-in | 11/8/2019 | 11/8/2019 | 11/8/2019 | P | PASS |
Brian Scoles
|
|
|
Noe- ###-####- 2 condensate R/I in wall ok- condensate installed all units- gas piping on roof secured to supports and regulators ok- need to see low pressure test to dishwashe before wall can be coveredr- went over with Noe onsite
|
Rough-in | 11/7/2019 | 11/8/2019 | 11/8/2019 | A | NR |
Brian Scoles
|
|
|
if questions call Noe @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann- gas test needs max 100lb gauge and over 60 psi- went over with Noe onsite - I rescheduled for pm inspection
|
Issue PAID IN FULL permit | | | 4/25/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 4/23/2019 | | DONE |
|
|
|
This permit was created on the web by Stacia Haumann
|