Final | 1/31/2020 | 1/31/2020 | 1/31/2020 | P | PASS |
Ben Livingston
|
|
|
|
Final | 1/30/2020 | 1/31/2020 | 1/31/2020 | A | FAIL |
Ben Livingston
|
|
|
Please call Bryan at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum - Chad still hasnt recieved revised documentation -
|
Final | 1/28/2020 | 1/29/2020 | 1/29/2020 | A | FAIL |
Ben Livingston
|
|
|
Please call Bryan at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum - need updated balance and commisioning reports for final -
|
Final | 12/18/2019 | 12/18/2019 | 12/19/2019 | P | PART |
Ben Livingston
|
|
|
Please call Bryan at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
Items of concern:
F-112 unit undersized for CFM values shown on drawing (if the drawings are revised we will need the new drawings submitted so our documents are updated as well). F-113 outdoor units needs to be repaired before unit can operate at high speed. F-103 unit is oversized for the connected CFM load. F-202 unit is only achieving 78% of designed air flow. FC-101 and FC-115 Not operating. Living room A201 missing balance dampers in 6 of the supply branch lines No access to damper in dining room A154- - temp C.O. okay -
|
Rough-in | 12/13/2019 | 12/16/2019 | 12/16/2019 | A | PASS |
Ben Livingston
|
|
|
Please call Bryan at least 30 min prior to inspection, thank you. Phone #: ###-#### Inspection requested via web by Rhonda Marcum - need uv protection on armaflex, and comisioning report approved for final -
|
Final | 11/21/2019 | 11/21/2019 | 11/21/2019 | P | NR |
Ben Livingston
|
|
|
Please call Bryan at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum - armaflex needs uv protection - - condencers need locking caps - - all 2nd condensate drains on furnaces need tobe run - - not all gardian systems on ranges are complete - - industrial dryer vents need tobe supported - - louver in laundryroom isnt wired up - - need to submit commisioning report to Chad for approval -
|
Rough-in | 10/17/2019 | 10/17/2019 | 10/17/2019 | P | PASS |
Ben Livingston
|
|
|
1st floor Area A. Please call Bryan at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum - 1st floor above grid okay -
|
Rough-in | 7/15/2019 | 7/16/2019 | 7/16/2019 | A | PASS |
Ben Livingston
|
|
|
Please call Bryan at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum -- area B 1st floor corridors and rooms above lids okay--
|
Rough-in | 7/11/2019 | 7/11/2019 | 7/11/2019 | P | PASS |
Ben Livingston
|
|
|
Please call Bryan at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum 2nd floor area B restrooms
|
Rough-in | 7/9/2019 | 7/9/2019 | 7/9/2019 | P | PASS |
Ben Livingston
|
|
|
Please call Bryan at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum 1st floor smoke dampers okay, guest rest room fans okay, all above lids 1st floor okay
|
Rough-in | 6/26/2019 | 6/26/2019 | 6/26/2019 | P | PASS |
Ben Livingston
|
|
|
Please call Bryan at least 30 min prior to inspection, thank you. Phone #: ###-#### Inspection requested via web by Rhonda Marcum - kitchen and dinning room above lid okay-
|
Rough-in | 6/18/2019 | 6/19/2019 | 6/19/2019 | P | PASS |
Ben Livingston
|
|
|
Please call Bryan at least 30 min prior to inspection, thank you. Phone #: ###-#### Inspection requested via web by Rhonda Marcum -2nd fllor area A corridors, geust bathroom lids okay- -2nd floor dryer vent walls NOT READY--- -1st floor area A section 1 restroom lids okay
|
Rough-in | 6/12/2019 | 6/13/2019 | 6/13/2019 | P | PASS |
Ben Livingston
|
|
|
Please call Bryan at least 30 min prior to inspection, thank you. Phone #: ###-#### Inspection requested via web by Rhonda Marcum 2nd floor duct seal okay, 1st floor area B flue okay
|
Rough-in | 6/6/2019 | 6/7/2019 | 6/7/2019 | A | PART |
Ben Livingston
|
|
|
Please call Bryan at least 30 min prior to inspection, thank you. Phone #: ###-#### Inspection requested via web by Rhonda Marcum -area A 1st floor soffits and restrooms okay 2nd floor fire smoke damper angles need to be tighter, clearance ok on 2
|
Rough-in | 5/31/2019 | 5/31/2019 | 5/31/2019 | P | PART |
Ben Livingston
|
|
|
Please call Bryan at least 30 minutes prior to inspection, thank you. Phone #: ###-#### Inspection requested via web by Rhonda Marcum 2nd floor area A zone 1 part duct seal okay
|
Rough-in | 5/9/2019 | 5/10/2019 | 5/10/2019 | A | PART |
Ben Livingston
|
|
|
Please call Bryan 30 min prior to inspection, thank you. Phone #: ###-#### Inspection requested via web by Rhonda Marcum flues 1st floor ceiling to 2nd floor attic
|
Issue PAID IN FULL permit | | | 4/26/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 4/26/2019 | | DONE |
|
|
|
This permit was created on the web by Rhonda Marcum
|
First Notice | 1/31/2020 | 1/31/2020 | | | |
Ben Livingston
|
|
|
|