Mec-Aging Inspection | 5/22/2020 | 5/22/2020 | 5/22/2020 | | DONE |
Chad Schwendiman
|
|
|
Expired
|
DOC - Permit Expired | 5/22/2020 | 5/22/2020 | 5/22/2020 | A | PASS |
Chad Schwendiman
|
|
|
|
Final | 2/21/2020 | 2/28/2020 | 2/26/2020 | P | CANC |
Jack Reynolds
|
|
|
Please call Jacob when you are on your way. Phone #: ###-#### >> Inspection requested via web by Misty McNabb Inspection cancelled from web by: Misty McNabb
|
Mec-Aging Inspection | 2/19/2020 | 2/19/2020 | 2/19/2020 | | FAIL |
Jack Reynolds
|
|
|
Permit has not been active since failing inspection on 7-5-19. If corrections have been made schedule inspection with owner. Permit will expire at next mechanical aging inspection if not active.
|
Mec-Aging Inspection | 11/20/2019 | 11/20/2019 | 11/20/2019 | | FAIL |
Jack Reynolds
|
|
|
Fail schedule inspection if corrections have been made. Permit hasn't been active since 7-5-19
|
Rough-in | 7/3/2019 | 7/5/2019 | 7/5/2019 | P | FAIL |
Jack Reynolds
|
|
|
Please notify Jacob 20 minutes ahead: ###-#### Phone #: ###-#### Inspection requested via web by Melissa Skinner - Both RTU's need sediment traps installed on gas line - need to see proof of RTU's having smoke detectors operational - east RTU needs flue extended above make up air intake
|
Issue PAID IN FULL permit | | | 5/3/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 5/3/2019 | | DONE |
|
|
|
This permit was created on the web by Melissa Skinner
|