Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberMEC19-01954
StatusFinaled
Name LEGENDS MECHANICAL LLC
Site Address 2133 S AMY AVE
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete HVAC Installation: complete hvac install
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final8/27/20198/28/20198/28/2019APASS
DetailsJack Reynolds
Duct blast witness @ 9:30 Phone #: ###-#### Inspection requested via web by Gary Reeves
- duct blast ok
- final ok
Rough-in5/31/20196/3/20196/3/2019APASS
DetailsJack Reynolds
Phone #: ###-#### Inspection requested via web by Gary Reeves
- R/I ok
- check dryer vent termination at final core drilling still needed to be performed
Pressure Test5/31/20196/3/20196/3/2019APASS
DetailsJack Reynolds
Phone #: ###-#### Inspection requested via web by Gary Reeves
2- 5lb flue pressure tests ok
-20 lb gas pressure test ok
Pressure Test5/30/20195/31/20195/31/2019PCANC
DetailsJack Reynolds
Phone #: ###-#### Inspection requested via web by Gary Reeves
Rough-in5/30/20195/31/20195/31/2019PCANC
DetailsJack Reynolds
Phone #: ###-#### Inspection requested via web by Gary Reeves
Rough-in5/28/20195/29/20195/29/2019AFAIL
DetailsJack Reynolds
Phone #: ###-#### Inspection requested via web by Gary Reeves
- crawl needs finished
- water heater vent needs nail plates installed
- water heater flue cant be cell core PVC
- furnace flue test fail
- great room is missing a supply run
- dryer vent downstairs needs another nail plate/ dyrer vent length is too long
- downstairs exhaust fan ducting in wall needs replaced due to being smashed and deformed
Pressure Test5/28/20195/29/20195/29/2019AFAIL
DetailsJack Reynolds
Phone #: ###-#### Inspection requested via web by Gary Reeves
- furnace 5lb flue pressure test fail
- water heater flue pressure test needs to be re tested when proper pvc is installed
- 20lb gas pressure test ok
Rough-in5/24/20195/28/20195/28/2019PCANC
DetailsJack Reynolds
Phone #: ###-#### >> Inspection requested via web by Gary Reeves Inspection cancelled from web by: Gary Reeves
Pressure Test5/24/20195/28/20195/28/2019PCANC
DetailsJack Reynolds
Phone #: ###-#### >> Inspection requested via web by Gary Reeves Inspection cancelled from web by: Gary Reeves
Issue PAID IN FULL permit  5/10/2019 DONE
Payment received via Govolutions
Application received  5/10/2019 DONE
This permit was created on the web by Gary Reeves