Final | 9/6/2019 | 9/9/2019 | 9/9/2019 | P | PASS |
Jack Reynolds
|
|
|
Please call when you are on the way so we can contact homeowner and make sure she is there. Will be working with landscapers in the back so if she doesn''t answer please go around back. ###-#### Advised homeowner of the need for electrician to pull permit for electrical work completed Phone #: ###-#### Inspection requested via web by Dan McFate - final ok
|
Final | 8/2/2019 | 8/2/2019 | 8/2/2019 | P | NH |
Jack Reynolds
|
|
|
Please call ###-#### when you are on the way so we can make sure someone is home or meet you there Phone #: ###-#### Inspection requested via web by Dan McFate - no access to home left notice on front door - still need to see electrical permit
|
Final | 7/11/2019 | 7/12/2019 | 7/12/2019 | A | FAIL |
Jack Reynolds
|
|
|
Please call when you are on the way so we can meet you there. ###-#### Phone #: ###-#### Inspection requested via web by Dan McFate - line set insulation at indoor unit and outdoor unit needs rips repaired - line set at the outdoor unit needs UV protection - A/C breaker size is too large - co detectors need install near bedrooms - need to see electrical permit pulled for new A/C - sediment trap needs installed after shut off valve
|
Issue PAID IN FULL permit | | | 6/21/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 6/21/2019 | | DONE |
|
|
|