Final | 8/30/2019 | 9/3/2019 | 9/3/2019 | P | PASS |
Brian Scoles
|
|
|
Philip Phone #: ###-####- furnace a/c coil co ok
|
Pressure Test | 8/26/2019 | 8/26/2019 | 8/26/2019 | P | NH |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Monica Lindsay- no one answered door- left notice
|
Final | 8/21/2019 | 8/22/2019 | 8/22/2019 | P | FAIL |
Brian Scoles
|
|
|
will be home in the afternoon Phone #: ###-#### Inspection requested via web by Monica Lindsay- 1- need uv protection outside on lineset at a/c- 2- need to seal lineset thru foundation weather/rodent proof 3- need sediment trap on gas line between shut off valve and furnace 4- flue needs rerouted to maintain grade and omit horizontal off furnace 5- need to firecaulk penetrations on lineset by furnace into crawl
|
Final | 8/15/2019 | 8/16/2019 | 8/16/2019 | P | NH |
Brian Scoles
|
|
|
WILL BE HOME AT 2:00 PM CALL AHEAD Phone #: ###-#### Inspection requested via web by Monica Lindsay- called number listed twice no answer- went by no one home
|
Final | 8/15/2019 | 8/15/2019 | 8/15/2019 | P | CANC |
Brian Scoles
|
|
|
CALL AHEAD, WILL BE HOME AFTER 2pm Phone #: ###-#### >> Inspection requested via web by Monica Lindsay Inspection cancelled from web by: Monica Lindsay
|
Issue PAID IN FULL permit | | | 6/25/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 6/25/2019 | | DONE |
|
|
|
This permit was created on the web by Monica Lindsay
|