Final | 9/4/2019 | 9/5/2019 | 9/5/2019 | A | PASS |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by Lynn Johnston - final ok
|
Rough-in | 7/8/2019 | 7/8/2019 | 7/8/2019 | P | PASS |
Jack Reynolds
|
|
|
pressure test Phone #: ###-#### Inspection requested via web by Lynn Johnston - R/I ok
|
Rough-in | 7/3/2019 | 7/3/2019 | 7/3/2019 | P | FAIL |
Jack Reynolds
|
|
|
Pressure test Phone #: ###-#### Inspection requested via web by Lynn Johnston - need stamped man J onsite - range vent needs supported -transfer air in laundry room - exhaust fan connection needs sealed - condensate line needs grade before going vertical down the wall
|
Issue PAID IN FULL permit | | | 7/3/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 7/3/2019 | | DONE |
|
|
|
This permit was created on the web by Lynn Johnston
|