Mec-Aging Inspection | 7/7/2020 | 7/7/2020 | 7/7/2020 | | CANC |
Ben Livingston
|
|
|
wip
|
Mec-Aging Inspection | 4/7/2020 | 4/7/2020 | 4/7/2020 | | CANC |
Ben Livingston
|
|
|
wip
|
Final | 1/7/2020 | 1/7/2020 | 1/7/2020 | A | FAIL |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by Greg Sutton 3- condensate line needs supported on outside of house/ penetrations need sealed - line sets need insulation finished/ UV protection installed and penetration needs sealed - outdoor HP needs 3" pop ups
|
Fees Due Hold | 7/13/2019 | | 1/3/2020 | | DONE |
|
|
|
|
Conference | 7/11/2019 | 7/11/2019 | 7/11/2019 | A | FAIL |
Ben Livingston
|
|
|
Mini split rough in correction and bathroom vent correction Late morning if possible Phone #: ###-#### Inspection requested via web by Greg Sutton ---still need to add exhaust fans to permit---
|
Rough-in | 7/11/2019 | 7/11/2019 | 7/11/2019 | P | PASS |
Ben Livingston
|
|
|
Mini split rough in correction and bathroom vent correction Late morning if possible Phone #: ###-#### Inspection requested via web by Greg Sutton
|
Rough-in | 7/10/2019 | 7/10/2019 | 7/10/2019 | P | FAIL |
Ben Livingston
|
|
|
2nd floor rough in mini splits Phone #: ###-#### Inspection requested via web by Greg Sutton --condensate piping not approved material, need 3/4" pvc. -- exhaust duct needs 6" roof jack not 4". -- exhaust duct needs hangers. -- on final energy star fan needs correct timer for ventalation. -- need to add exhaust fans to permit
|
Issue PAID IN FULL permit | | | 7/8/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 7/8/2019 | | DONE |
|
|
|
This permit was created on the web by Greg Sutton
|