Permit Information
Permit NumberMEC19-02957
StatusFinaled
Name RM MECHANICAL
Site Address 711 N CURTIS RD
Project Name 
Customer NumberD19-051
ePlanReviewNo
Description
New: Class one hood(s) install
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
First Notice7/22/20197/22/20197/27/2020 DONE
DetailsBrian Scoles
This permit finaled on the web by RM Mechanical
Print Statement  3/9/2020 DONE
Final7/22/20197/22/20197/22/2019PPASS
DetailsBrian Scoles
Pat Nichols site contact Phone #: ###-#### Inspection requested via web by RM Mechanical- final ok- card signed
Final7/10/20197/11/20197/11/2019PPART
DetailsBrian Scoles
kitchen hood // James Phone #: ###-####- need all appliance set into place under class 1 hood- need air balance report onsite for all hoods- left side of north hood needs 18" ss panels installed in ceiling can not have ceiling tile within 18" went over with general onsite- need to uv protect arma flex on roof and seal water tight on line set penetration- call in when ready- dishwasher hood ok-
Issue PAID IN FULL permit  7/10/2019 DONE
Payment received via Govolutions
Owner Supplied Equipment  7/10/2019  
Application received  7/10/2019 DONE
This permit was created on the web by RM Mechanical