First Notice | 9/18/2019 | 9/18/2019 | 2/3/2020 | | DONE |
Brian Scoles
|
|
|
This permit finaled on the web by Arcadio Martinez
|
Final | 9/17/2019 | 9/18/2019 | 9/18/2019 | A | PASS |
Brian Scoles
|
|
|
Arcadio-final needed-gas pressure was inspected on MEC19-04124 Phone #: ###-####- final ok card sigmed
|
Final | 9/17/2019 | 9/17/2019 | 9/17/2019 | A | FAIL |
Brian Scoles
|
|
|
Door will be unlocked Phone #: ###-#### Inspection requested via web by Arcadio Martinez- need to secure all new gas piping to new supports on roof- need to add gas piping to valuation of permit and pay fee
|
Final | 9/13/2019 | 9/16/2019 | 9/16/2019 | P | PART |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Arcadio Martinez- need pressure test on whole gas line- need to update valuation for gas piping that wasnt included and pay fee- rest is good- will final out once pressure test is completed and passed- need to secure gas piping on roof to supports on all new piping installed
|
Rough-in | 7/11/2019 | 7/12/2019 | 7/12/2019 | P | PASS |
Brian Scoles
|
|
|
There is a lock box at the front door, code is 208 Phone #: ###-#### Inspection requested via web by Arcadio Martinez- R/I ok- will need to add 10" damper to supply line where sidewall register is by final- need approved prints onsite at final- contractor will be onsite for roof access at final
|
Issue PAID IN FULL permit | | | 7/11/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 7/11/2019 | | DONE |
|
|
|
This permit was created on the web by Arcadio Martinez
|