Information based on query as of Tuesday, July 23, 2024.
Permit Information
Permit NumberMEC19-02981
StatusFinaled
Name ACCO ENGINEERED SYSTEMS
Site Address 146 S COLE RD
Project NameBuilding #3
Customer Number 
ePlanReviewNo
Description
Alteration: (Building #3) Replace 9 RTU's at this building. (Reference fees paid on MEC18-05024) //7-11-19 LEG
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final8/13/20198/13/20198/13/2019PPASS
DetailsBrian Scoles
Please contact Steve Kingsmore with any questions at ###-####. Phone #: ###-#### Inspection requested via web by Joshua Bennett- final ok
Final7/16/20197/17/20197/17/2019APART
DetailsBrian Scoles
Please contact Curt Osborne for access coordination and ladder. Please contact Curt Osborne at ###-#### Phone #: ###-#### Inspection requested via web by Joshua Bennett- need to srap all gas piping to supports that was extended or added on to on roof- RTU 5, 12 and 13 need plumbing vents extended 3 feet higher than economizer and check metal snorkel- need to add p trap on RTU 6
Issue PAID IN FULL permit  7/15/2019 DONE
Application received  7/11/2019  
First Notice8/13/20198/13/2019   
DetailsBrian Scoles