Permit Information
Permit NumberMEC19-03096
StatusFinaled
Name YMC INC
Site Address 2909 W ELDER ST
Project Name 
Customer Number2107841
ePlanReviewNo
Description
Addition: PTAC units, exhaust fans, one split system, and duct work.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/16/20203/16/20203/16/2020PPASS
DetailsJack Reynolds
Please call Bryan at least 30 min prior to inspection, thank you!! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
- final ok
- occ card signed
Final3/11/20203/12/20203/12/2020ACANC
DetailsJack Reynolds
Please call Bryan at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
- check R/I inspection from the afternoon of
3-11-20 for correction notice
Rough-in3/11/20203/11/20203/11/2020PFAIL
DetailsJack Reynolds
Please call Bryan at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
- should have been a final not a R/I
- A/C's need locking caps installed on service ports
- line set penetrations need sealed and line set insulation needs UV protections
- all fire damper access doors need installed and all dampers need labeled
- commerical dryers need 2" min clearances to combustibles and insulation sheild installed in wall
- dryers vent length is too long on both dryers
- damper interlock with dryers needs adjusted
Rough-in2/25/20202/26/20202/26/2020APASS
DetailsJack Reynolds
1st floor Men''s and Women''s restrooms. Please call Bryan at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested
via web by Rhonda Marcum
- 2 bathrooms 1st floor R/I ok
Rough-in2/20/20202/20/20202/20/2020PFAIL
DetailsJack Reynolds
Rough-in on men''s and women''s bathroom, final on 2nd, 3rd, and 4th floor if possible. Please call Bryan at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
- plan mod is under review
Rough-in1/28/20201/30/20201/30/2020APASS
DetailsBrian Scoles
Please call Bryan at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum- lobby and hallway ok- 2 fire damper angles ok- access on duct and ceiling ok- duct insulation installed 2 locations- ok for cover
Rough-in1/27/20201/28/20201/28/2020PFAIL
DetailsJack Reynolds
Rough in for first floor lobby and hallways, please call Bryan at least 30 in prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
- hard lid cover in lobby and hallway 1st floor fail
- fire dampers missing retaining angles
- fire damper in duct access door needs moved for access from ceiling
- two locations of duct insulation need installed
Conference1/7/20201/8/20201/8/2020APASS
DetailsJack Reynolds
Please call Bryan at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
Rough-in1/8/20201/8/20201/8/2020APART
DetailsJack Reynolds
Please call Bryan at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
2- 8" F/S damper clearances ok
all bathroom hard lids ok for cover other than two guest bathrooms in the corridor next to gym.
- talked with HVAC contractor and general about fire dampers in ceiling/floor assembly per approved drawnings. Contractor says they will not be able to fit a fire damper in ceiling space. Explained that they will need to have this issue looked at by design professional and then reviewed by city before moving foward.
CHANGE STATUS TO (ISS)  1/7/2020 DONE
Monica from YMC called because she was having trouble scheduling FNL inspection, there was no activity showing why it was final, ok to re-opened per Tisha
Rough-in12/20/201912/23/201912/23/2019AFAIL
DetailsJack Reynolds
Please call Bryan at least 30 min prior to inspection, thank you, Merry Christmas! Phone #: ###-#### Inspection requested via web by Rhonda Marcum

- duct seal ok for insulation
- two 8" F/S dampers need proper clearances
- two exhaust fans penetrating ceiling/floor assembly need dampers and access doors installed
- two exhaust flues for commerical dryers not installed yet
Rough-in10/15/201910/16/201910/16/2019APART
DetailsJack Reynolds
2nd, 3rd,; 4th floor exhaust rough in. Please call Bryan at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
- 2nd/3rd/4th floor exhaust ducting R/I ok
Rough-in10/3/201910/3/201910/3/2019PFAIL
DetailsJack Reynolds
2nd ; 3rd floor exhaust fans, 4th floor radiant dampers. Please call Bryan at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
- exhaust fans are not installed per prints on 2nd, 3rd and 4th floor
Rough-in7/30/20198/1/20198/1/2019APASS
DetailsJack Reynolds
Please call Delroy at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
3- 5lb flue pressure test for water heater ok
1- 5lb flue pressure test for furnace ok
- line sets on 1st floor ok
Issue PAID IN FULL permit  7/17/2019 DONE
Payment received via Govolutions
Application received  7/17/2019 DONE
This permit was created on the web by Rhonda Marcum
First Notice3/16/20203/16/2020   
DetailsJack Reynolds