Final | 11/25/2019 | 11/26/2019 | 11/26/2019 | P | PASS |
Ben Livingston
|
|
|
garage code 0041 Phone #: ###-#### Inspection requested via web by Joseph Profitt
|
Final | 11/25/2019 | 11/25/2019 | 11/26/2019 | P | FAIL |
Ben Livingston
|
|
|
Garage code 0041 Phone #: ###-#### Inspection requested via web by Joseph Profitt - need blocking caps on condencers - - furnace and water heater needs combustion air in garage mechanical closet -
|
Final | 11/21/2019 | 11/22/2019 | 11/22/2019 | P | NH |
Ben Livingston
|
|
|
Phone #: ###-#### Inspection requested via web by Joseph Profitt - no access, condencers need locking caps -
|
Rough-in | 9/9/2019 | 9/9/2019 | 9/9/2019 | P | PASS |
Ben Livingston
|
|
|
Phone #: ###-#### Inspection requested via web by Joseph Profitt
|
Rough-in | 9/4/2019 | 9/5/2019 | 9/5/2019 | P | FAIL |
Ben Livingston
|
|
|
Phone #: ###-#### Inspection requested via web by Joseph Profitt - correction not made, back draft damper isnt a fire damper-
|
Rough-in | 8/29/2019 | 8/30/2019 | 8/30/2019 | A | FAIL |
Ben Livingston
|
|
|
Phone #: ###-#### Inspection requested via web by Joseph Profitt - fresh air on 2nd floor unit need a fire damper or a 1 hr rated grille per wui zone A-
|
Pressure Test | 8/29/2019 | 8/30/2019 | 8/30/2019 | A | PASS |
Ben Livingston
|
|
|
Phone #: ###-#### Inspection requested via web by Joseph Profitt - 20lb,5lbx2-
|
Issue PAID IN FULL permit | | | 8/29/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 8/29/2019 | | DONE |
|
|
|
This permit was created on the web by Joseph Profitt
|