Final | 12/9/2019 | 12/9/2019 | 12/9/2019 | P | PASS |
Jack Reynolds
|
|
|
ReInspect Phone #: ###-#### Inspection requested via web by Randy Hart - final ok
|
Final | 12/5/2019 | 12/6/2019 | 12/5/2019 | P | CANC |
Jack Reynolds
|
|
|
Phone #: ###-#### >> Inspection requested via web by Randy Hart Inspection cancelled from web by: Randy Hart
|
Final | 12/4/2019 | 12/5/2019 | 12/5/2019 | P | FAIL |
Jack Reynolds
|
|
|
re inspection Phone #: ###-#### Inspection requested via web by Randy Hart - need to see combustion openings in laundry room door - A/C locking caps installed
|
Final | 12/2/2019 | 12/4/2019 | 12/4/2019 | A | FAIL |
Chad Schwendiman
|
|
|
2468 Phone #: ###-#### Inspection requested via web by Randy Hart - Need locking access caps on refrigeration piping, Water heater not vented, gas piping isn't connected to the water heater, Laundry room alone doesn't have enough voulume for combustion air for furnace closet as a result it needs 2 openings communicating with the rest of the 2nd floor for combustion air for the furnace closet.
|
Final | 11/26/2019 | 12/2/2019 | 12/2/2019 | A | CANC |
Jack Reynolds
|
|
|
Phone #: ###-#### >> Inspection requested via web by Randy Hart Inspection cancelled from web by: Randy Hart
|
Rough-in | 10/16/2019 | 10/16/2019 | 10/16/2019 | P | PASS |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by Randy Hart - R/I ok - lower combustion air in laundry room door will be seen at final
|
Rough-in | 10/15/2019 | 10/16/2019 | 10/16/2019 | A | CANC |
Jack Reynolds
|
|
|
Phone #: ###-#### >> Inspection requested via web by Randy Hart Inspection cancelled from web by: Randy Hart
|
Rough-in | 10/11/2019 | 10/15/2019 | 10/15/2019 | A | FAIL |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by Randy Hart - need city approved man j onsite - fresh air needs ran to furnace return plenum - combustion air for furnace needs to be per IECC R402.4.4 or combustion air needs taken through high/low grilles inside place
|
Pressure Test | 10/11/2019 | 10/15/2019 | 10/15/2019 | A | PASS |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by Randy Hart - 20lb gas pressure test ok - tagged meter location
|
Issue PAID IN FULL permit | | | 9/9/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 9/9/2019 | | DONE |
|
|
|
This permit was created on the web by Randy Hart
|