Final | 3/6/2020 | 3/9/2020 | 3/9/2020 | A | PASS |
Brian Scoles
|
|
|
RANDY Phone #: ###-####- final ok
|
Card not on site to sign | 3/9/2020 | 3/9/2020 | 3/9/2020 | A | PASS |
Brian Scoles
|
|
|
RANDY Phone #: ###-####- no card onsite to sign
|
Final | 3/4/2020 | 3/5/2020 | 3/5/2020 | A | FAIL |
Brian Scoles
|
|
|
repairs made, duct insulated strap installed will attach air balance for hood thank you Phone #: ###-#### Inspection requested via web by Randy Keuhey- need air balance report onsite- reschedule- rest is good
|
Final | 2/6/2020 | 2/7/2020 | 2/7/2020 | A | PART |
Brian Scoles
|
|
|
please call randy Phone #: ###-#### Inspection requested via web by Randy Keuhey- need installation instructions on oven- need air balance report- insulate mau duct- call in final when ready
|
Rough-in | 2/7/2020 | 2/7/2020 | 2/7/2020 | A | PASS |
Brian Scoles
|
|
|
please call randy Phone #: ###-#### Inspection requested via web by Randy Keuhey- R/I ok- seal on duct ok- need to insulatemake up air duct- need strap on class 2 exhaust duct above grid- need oven installation instruction onsite- need air balance report- no ducting change to dining area or bathrooms
|
Issue PAID IN FULL permit | | | 11/4/2019 | | DONE |
|
|
|
not sure how this didn't get issued when paid for
|
Application received | | | 9/24/2019 | | DONE |
|
|
|
This permit was created on the web by Randy Keuhey
|
First Notice | 3/9/2020 | 3/9/2020 | | | |
Brian Scoles
|
|
|
|