Final | 1/6/2020 | 1/7/2020 | 1/7/2020 | A | PASS |
Brian Scoles
|
|
|
CORRECTION MADE MAN J INSIDE INFORMATION BIN BY ELECTRICAL PANEL LOCK BOX CODE 0124 Phone #: ###-#### Inspection requested via web by Oleg Chervak
|
Final | 1/3/2020 | 1/3/2020 | 1/3/2020 | P | FAIL |
Brian Scoles
|
|
|
GARAGE CD 1234 Phone #: ###-#### Inspection requested via web by Oleg Chervak 1- approved man j onsite 2- condensate to washer box needs completed 3- seal exterior gas line penetration at meter
|
Rough-in | 10/2/2019 | 10/3/2019 | 10/3/2019 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak- R/I ok
|
Final | 10/2/2019 | 10/3/2019 | 10/3/2019 | P | CANC |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak
|
Rough-in | 10/1/2019 | 10/2/2019 | 10/2/2019 | P | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak- not all corrections made- see notice on sliding door
|
Pressure Test | 10/1/2019 | 10/2/2019 | 10/2/2019 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak- already completed
|
Rough-in | 10/1/2019 | 10/1/2019 | 10/1/2019 | P | CANC |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak- wont be ready y time i come back by- reschedule
|
Pressure Test | 10/1/2019 | 10/1/2019 | 10/1/2019 | P | CANC |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak- already completed
|
Rough-in | 9/30/2019 | 10/1/2019 | 10/1/2019 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak- 1- need ladder provided by contractor to access furnace in attic 2- framing needs completed around b vent 2nd floor and draftstop installled 3- exhaust fan 2nd floor shall terminate 4 feet from property line 4- need to insulate bare metal in att supply and r/a 5- need to seal dryer duct to termination box 6- need 6" fresh air installed and maintain 10 feet from exhaust ducts 7- flue shall be b vent off furnace remove single wall pipe/fitting left notice
|
Pressure Test | 9/30/2019 | 10/1/2019 | 10/1/2019 | A | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak- 20lb gas pass tagged meter location
|
Issue PAID IN FULL permit | | | 9/30/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 9/30/2019 | | DONE |
|
|
|
This permit was created on the web by Oleg Chervak
|