Information based on query as of Tuesday, July 23, 2024.
Permit Information
Permit NumberMEC19-04335
StatusFinaled
Name ALL AMERICAN HEATING & A/C LLC
Site Address 9056 W EMERALD ST
Project Name 
Customer Number 
ePlanReviewNo
Description
New: I’m doing the roof top units and extended plenum for gyro shack and bathroom areas. I’m also connecting the ducting from the exhaust hood and make up air unit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final12/13/201912/16/201912/16/2019APASS
DetailsBrian Scoles
Inspection requested via web by jeff jedlick- final ok - card signed
Rough-in12/6/201912/6/201912/6/2019PPASS
DetailsBrian Scoles
Inspection requested via web by jeff jedlick- R/I ok- registers flex and insulation ok- ok for ceiling tiles- need air balance report onsite for hoo and MAU- need condensate drains on RTUs- need to label f/s damper access doors by final
Conference12/5/201912/5/201912/5/2019PDONE
DetailsBrian Scoles
Call when you have a minute Inspection requested via web by jeff jedlick-
Rough-in12/4/201912/4/201912/4/2019APART
DetailsBrian Scoles
will need engineer approval on mau ducting that has changed sizing and routing
Rough-in11/25/201911/25/201911/25/2019APASS
DetailsBrian Scoles
2 fire smoke damper clearances ok-
Rough-in11/20/201911/20/201911/20/2019PPART
DetailsBrian Scoles
I’m here all day, like to meet late as possible... Phone #: ###-#### Inspection requested via web by jeff jedlick- seal on remaining duct ok- ok to insulate- need to look at f/s damper clearances next inspection
Conference10/28/201910/28/201910/28/2019ADONE
DetailsBrian Scoles
Want to go over installation instructions on smoke/fire damper Inspection requested via web by jeff jedlick- went over fire/smoke damper installation
Rough-in10/25/201910/25/201910/25/2019PPASS
DetailsBrian Scoles
Inspection requested via web by jeff jedlick- bath room hardlids ok to cover- seal and insulation ok in bath room
Rough-in10/24/201910/24/201910/24/2019PCANC
DetailsBrian Scoles
Inspection requested via web by jeff jedlick- will reschedule per phone call
Conference10/23/201910/23/201910/23/2019PDONE
DetailsBrian Scoles
Inspect the bathroom ducting and fire wall penetration. 208 801 3772 Shawn general on the job Phone #: ###-#### Inspection requested via web by jeff jedlick- went over fire damper installation instructions- needs sleeve extending out on each side of wall- call in R/I when ready
Issue PAID IN FULL permit  10/1/2019 DONE
Payment received via Govolutions
Application received  10/1/2019 DONE
This permit was created on the web by jeff jedlick
First Notice12/16/201912/16/2019   
DetailsBrian Scoles
First Notice12/16/201912/16/2019   
DetailsBrian Scoles