Final | 1/8/2020 | 1/9/2020 | 1/9/2020 | P | PASS |
Brian Scoles
|
|
|
MEC AND FIREPL Phone #: ###-#### Inspection requested via web by Oleg Chervak- HVAC and fireplace final ok
|
Rough-in | 10/15/2019 | 10/15/2019 | 10/15/2019 | P | PASS |
Brian Scoles
|
|
|
corrections made please come early afternoon, builder has called in for framing inspection as well. thank you -peter Phone #: ###-#### Inspection requested via web by Oleg Chervak- R/I ok HVAC and fireplace
|
Rough-in | 10/11/2019 | 10/14/2019 | 10/14/2019 | A | FAIL |
Brian Scoles
|
|
|
MEC AND FIREPL Phone #: ###-#### Inspection requested via web by Oleg Chervak 1- all exposed insulation in crawl on flex duct needs installed per installation instructions with vapor barrier 2- need to seal all spot welds on all supply and R/A boots 3- need to seal dryer duct to termination box 4- framing needs completed on fireplace and secured in to place 5- need fireplace installation instructions easily accessible behind glass now
- 6- need to secure b vent in attic---left notice front entry window
|
Pressure Test | 10/11/2019 | 10/14/2019 | 10/14/2019 | A | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak- 20lb gas pass tagged meter location
|
Issue PAID IN FULL permit | | | 10/2/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 10/2/2019 | | DONE |
|
|
|
This permit was created on the web by Oleg Chervak
|