Information based on query as of Tuesday, July 23, 2024.
Permit Information
Permit NumberMEC19-04438
StatusFinaled
Name LEGENDS MECHANICAL LLC
Site Address 9647 W MACAW ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete HVAC Installation: complete hvac install
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final1/8/20201/9/20201/9/2020PPASS
DetailsBrian Scoles
AC:2019 Phone #: ###-#### Inspection requested via web by Gary Reeves- final ok
Rough-in10/18/201910/18/201910/18/2019PPASS
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Gary Reeves- R/I ok
Pressure Test10/18/201910/18/201910/18/2019PPASS
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Gary Reeves
Rough-in10/16/201910/17/201910/17/2019PFAIL
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Gary Reeves-
1- need inert tape on gas line
2- need approved man j onsite
3- exhaust fan 2nd floor has trap in 4" duct needs to maintain grade from fan to roof
4- dryer duct can not run in 2x4 wall needs firred out or rerouted
5- ducting in crawl needs to maintain 4" off earth and bare metal needs insulated at zone damper

left correction notice front window
Pressure Test10/16/201910/17/201910/17/2019PPART
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Gary Reeves- 20lb gas pass tagged meter location- need inert tape on gas line penetration thru wall at meter location
Issue PAID IN FULL permit  10/4/2019 DONE
Payment received via Govolutions
Application received  10/4/2019 DONE
This permit was created on the web by Gary Reeves