Final | 10/14/2019 | 10/15/2019 | 10/15/2019 | P | PASS |
Jack Reynolds
|
|
|
Please call 1 hour before arrival. 208 284 7403 Phone #: ###-#### Inspection requested via web by Joe Creechley - furnace ac coil co ok
|
Final | 10/9/2019 | 10/10/2019 | 10/10/2019 | P | FAIL |
Jack Reynolds
|
|
|
Please call 208 284 7403 an hour before arriving to house.
Thank you. Phone #: ###-#### Inspection requested via web by Joe Creechley - gas line needs sediment trap after shut off valve - condensate pump needs safety wired in - A/C service ports need locking caps - line set needs UV protection installed
|
Final | 10/8/2019 | 10/9/2019 | 10/9/2019 | P | NH |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by Joe Creechley - no access to home left notice on front door
|
Issue PAID IN FULL permit | | | 10/8/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 10/8/2019 | | DONE |
|
|
|
This permit was created on the web by Joe Creechley
|