Final | 12/6/2019 | 12/9/2019 | 12/9/2019 | A | PASS |
Brian Scoles
|
|
|
Final inspection. Call Joe with any questions or issues please. Thank you!!!! Phone #: ###-#### Inspection requested via web by Misty McNabb- final ok- card signed
|
Final | 12/3/2019 | 12/3/2019 | 12/3/2019 | P | PART |
Brian Scoles
|
|
|
Please call Joe when on way!!!! Phone #: ###-#### Inspection requested via web by Misty McNabb- registers flex drain pan ok- ok for ceiling tiles- recall in when completed and air balance done
|
Rough-in | 11/15/2019 | 11/18/2019 | 11/18/2019 | A | PASS |
Brian Scoles
|
|
|
Should have been scheduled for 11/15 afternoon to follow up fail -- hoping you are still coming today. Please call Joe at ###-#### Phone #: ###-#### Inspection requested via web by Misty McNabb- R/I ok- ok to cover
|
Rough-in | 11/11/2019 | 11/13/2019 | 11/13/2019 | A | FAIL |
Brian Scoles
|
|
|
Please call Blake with Altecca upon arriving or if you need any information. Phone #: ###-#### Inspection requested via web by Misty McNabb- need all supply, Return and outside air duct sealed- need to meet class 0 or 1 on flex duct off exhaust fan or run in rigid pipe or approved materials- schedule shows rigid pipe to slot diffusers need engineer approval on way installed or install per prints- does secondary drain pan meet plenum rated material 25/50 smoke/flame spread ?
|
Fees Due Hold | 11/2/2019 | | 11/5/2019 | | DONE |
|
|
|
|
Issue PAID IN FULL permit | | | 10/15/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 10/15/2019 | | DONE |
|
|
|
This permit was created on the web by Misty McNabb
|