Information based on query as of Wednesday, June 19, 2024.
Permit Information
Permit NumberMEC19-04687
StatusFinaled
Name POWELL DAWN L
Site Address 2592 N DALTON LN
Project Name 
Customer Number 
ePlanReviewNo
Description
Homeowner Online - Alteration or Repair: Add gas heat 60k BTU to the shop near the residence; tie in to house gas line; trench to the shop and run gas line.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final12/28/201912/30/201912/30/2019APASS
DetailsBrian Scoles
final inspection of 75k gas heater installed in shop behind the residence.. The only discrepancy found in final inspection is I had to add a third metal barrier in the wall for against the installation for the double wall exhaust stainless pipe to exit-all complete. Any time after 10AM AM or PM please text or call is fine, thanks Phone #: ###-#### Inspection requested via web by ron powell- final ok
Final12/23/201912/24/201912/24/2019AFAIL
DetailsJack Reynolds
Request final inspection of 75k heater for detached shop. pressure test inspection complete on line to shop, 2nd inspection done line to unit. Gas line is now to the unit and its operating. Electrical inspection passed and complete. Available after 10AM please. ###-#### Phone #: ###-#### Inspection requested via web by ron powell
- need to installed insulation shield through wall to maintain 1" clearances to combustibles
Pressure Test12/19/201912/19/201912/19/2019PPASS
DetailsBrian Scoles
Request inspection of gas line pressure test. LIne runs from ditch to inside of shop terminating where the 75k btu heater will hang. first inspection of the gas line in the ditch is complete. This inspection is after the line was added inside the shop. Available after 10AM but please call or text, thanks, Ron Phone #: ###-#### Inspection requested via web by ron powell- 20lb gas pass whole system
Pressure Test12/11/201912/11/201912/11/2019PPASS
DetailsBrian Scoles
20lb gas pass underground only- ok for backfill
Pressure Test11/12/201911/13/201911/13/2019ANR
DetailsBrian Scoles
Ron Powell Phone #: ###-####- need 2 anadised riser installed plastic pipe can not be installed above ground and 30lb max gauge at 20psi for pressure test
Issue PAID IN FULL permit  11/5/2019 DONE
Payment received via Govolutions
Application received  10/17/2019 DONE
This permit was created on the web by ron powell