Final | 1/27/2020 | 1/27/2020 | 1/27/2020 | P | PASS |
Brian Scoles
|
|
|
Bj 573 0755 Inspection requested via web by william kerwin- final ok
|
Final | 1/20/2020 | 1/21/2020 | 1/21/2020 | P | FAIL |
Brian Scoles
|
|
|
Lock box 7777. Bj ###-#### Inspection requested via web by william kerwin 1- duct blast test and air balance reports onsite 2- fireplace installation instructions onsite none found 3- w/h flue needs 6" clearance to single wall pipe 4- approved man j onsite 5- seal exterior gas line penetrations
|
Rough-in | 10/24/2019 | 10/24/2019 | 10/24/2019 | P | PASS |
Brian Scoles
|
|
|
Bj 5730755 Inspection requested via web by william kerwin- R/I hvac and fireplace ok- need duct blast and airbalance at final
|
Rough-in | 10/23/2019 | 10/23/2019 | 10/23/2019 | P | FAIL |
Brian Scoles
|
|
|
Code 7777 Phone #: ###-#### Inspection requested via web by Teresa Costello 1- b vent for water heater is touching R/A ducting in attic 2- need horizontal framing above fireplace per installation instructions
|
Rough-in | 10/21/2019 | 10/22/2019 | 10/22/2019 | A | FAIL |
Brian Scoles
|
|
|
Acess code 7777 Inspection requested via web by william kerwin 1- need approved man j onsite approved from city none found 2- need ladder provided by contractor to access furn/coil in attic 3- need fireplace instructions readily available behind glass 4- Range ducting on this unit ???
left correction n otice front window
|
Pressure Test | 10/21/2019 | 10/22/2019 | 10/22/2019 | A | PASS |
Brian Scoles
|
|
|
Acess code 7777 Inspection requested via web by william kerwin- 20lb gas pass tagged meter location
|
Issue PAID IN FULL permit | | | 10/21/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 10/21/2019 | | DONE |
|
|
|
This permit was created on the web by william kerwin
|
First Notice | 1/27/2020 | 1/27/2020 | | | |
Brian Scoles
|
|
|
|