Mec-Request for Extension | 5/27/2020 | 5/27/2020 | 5/27/2020 | P | PASS |
Chad Schwendiman
|
|
|
Extension approved
|
Mec-Aging Inspection | 5/22/2020 | 5/22/2020 | 5/22/2020 | | FAIL |
Brian Scoles
|
|
|
contractor needs to schedule inspection that was noted will be completed in spring time- request extension if works ongoing
|
Pressure Test | 10/24/2019 | 10/25/2019 | 10/25/2019 | A | PART |
Brian Scoles
|
|
|
Dave Phone #: ###-####- 60lb gas pass from garage thru carport to house- retest whole system when works completed in spring- work ongoing
|
Pressure Test | 10/22/2019 | 10/23/2019 | 10/23/2019 | P | FAIL |
Brian Scoles
|
|
|
David Phone #: ###-####- need open tee between the 2 shut off valves per code IRC G2417.1.4 in garage- needs to be 60lb gas test on 100lb gauge max since meter is 2# system and gauge didnt zero out
|
Application received | | | 10/22/2019 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 10/22/2019 | | DONE |
|
|
|
|