Mec-Aging Inspection | 6/22/2020 | 6/22/2020 | 6/22/2020 | | PASS |
Jack Reynolds
|
|
|
Doc Permit Finaled ok
|
DOC - Permit Finaled | 6/22/2020 | 6/22/2020 | 6/22/2020 | A | PASS |
Jack Reynolds
|
|
|
Doc Permit Finaled ok
|
Final | 11/18/2019 | 11/19/2019 | 11/19/2019 | A | PART |
Jack Reynolds
|
|
|
Phamash Phone #: ###-#### - corrections ok - plumbing permit needs pulled before final on mechanical will be given
|
Final | 11/15/2019 | 11/15/2019 | 11/15/2019 | P | FAIL |
Jack Reynolds
|
|
|
Phamash Phone #: ###-#### - line set penetration needs sealed - A/C service ports need locking caps installed - furnace flue needs b vent installed where combustibles are closer than 6" - coil secondary condensate needs a wet switch installed -gas line needs sediment trap installed - couldn't access crawl builder said crawl access will be available at next inspection to check condensate and line set support
|
Issue PAID IN FULL permit | | | 11/15/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 11/15/2019 | | DONE |
|
|
|
This permit was created on the web by thomas nguyen
|