Final | 11/21/2019 | 11/22/2019 | 11/22/2019 | A | PASS |
Brian Scoles
|
|
|
please call homeowner 30 minutes ahead of time // homeowner number is ###-#### // homeowner is paul Phone #: ###-#### Inspection requested via web by Joseph Profitt- corrections made
|
Final | 11/19/2019 | 11/20/2019 | 11/20/2019 | A | FAIL |
Brian Scoles
|
|
|
please call homeowner 30 minutes ahead of time // homeowner number is ###-#### // homeowner is paul Phone #: ###-#### Inspection requested via web by Joseph Profitt 1- need locking caps on a/c service ports on condenser 2- need sediment trap between gas shutoff valve and furnace 3- need weather tight whip from disconnect to condenser outside
recall in final when ready
|
Final | 11/18/2019 | 11/19/2019 | 11/19/2019 | P | NH |
Ben Livingston
|
|
|
homeowner said he will be home until 4 pm Phone #: ###-#### Inspection requested via web by Joseph Profitt - no access -
|
Issue PAID IN FULL permit | | | 11/18/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 11/18/2019 | | DONE |
|
|
|
This permit was created on the web by Joseph Profitt
|