Information based on query as of Sunday, June 30, 2024.
Permit Information
Permit NumberMEC19-05378
StatusFinaled
Name LEGENDS MECHANICAL LLC
Site Address 9656 W MACAW ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete HVAC Installation: complete hvac install
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/5/20203/6/20203/6/2020APASS
DetailsBrian Scoles
Ac 3162 Phone #: ###-#### Inspection requested via web by Gary Reeves
Final3/3/20203/4/20203/4/2020PFAIL
DetailsBrian Scoles
AC: 3162 Phone #: ###-#### Inspection requested via web by Gary Reeves
1- single wall water heater flue needs 6" clearance to sheetrock
2- condenser pad needs to be level
3- need to support water heater flue
Rough-in12/6/201912/9/201912/9/2019PPASS
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Gary Reeves- R/I ok
Pressure Test12/9/201912/9/201912/9/2019PPASS
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Gary Reeves- 5lb flue pass
Pressure Test12/4/201912/5/201912/5/2019PPASS
DetailsChad Schwendiman
Phone #: ###-#### Inspection requested via web by Gary Reeves - 20lb gas pass
Rough-in12/4/201912/5/201912/5/2019PFAIL
DetailsChad Schwendiman
Phone #: ###-#### Inspection requested via web by Gary Reeves - Need 1" clearance between flex duct and b-vent in the attic, b-vent is reverse graded in the attic, Need to seal duct where fresh air taps into return.
Issue PAID IN FULL permit  11/26/2019 DONE
Payment received via Govolutions
Application received  11/26/2019 DONE
This permit was created on the web by Gary Reeves