Final | 3/23/2020 | 3/23/2020 | 3/23/2020 | P | PASS |
Brian Scoles
|
|
|
Bj 5730755 Inspection requested via web by william kerwin- final ok
|
Final | 3/18/2020 | 3/19/2020 | 3/19/2020 | A | FAIL |
Brian Scoles
|
|
|
Bj 5730755. Code 7777 Inspection requested via web by william kerwin 1- range duct needs vented to outside 2- need locking caps on heat pump service ports 3- need to seal lineset penetration downstairs in closet to outside
talked to BJ by phone
|
Rough-in | 1/27/2020 | 1/27/2020 | 1/27/2020 | P | PASS |
Brian Scoles
|
|
|
Bj 2085730755 Inspection requested via web by william kerwin- R/I ok- corrections made
|
Rough-in | 1/23/2020 | 1/24/2020 | 1/24/2020 | A | FAIL |
Jack Reynolds
|
|
|
lockbox code is 7777. bj ###-#### Inspection requested via web by william kerwin - 2nd floor bathroom exhaust needs uncovered and terminated outside in approved manner - toe kick in kitchen needs ducted out - fireplace installation instructions -CSST needs full striker plates where within 2' of stud edge and half striker plates everywhere else - secondary drain on coil needs wetswitch installed by final and pump safety wired
|
Pressure Test | 1/23/2020 | 1/24/2020 | 1/24/2020 | A | PASS |
Jack Reynolds
|
|
|
lockbox code is 7777. Inspection requested via web by william kerwin - 20lb gas pressure test ok - tagged meter location
|
Issue PAID IN FULL permit | | | 1/23/2020 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 1/23/2020 | | DONE |
|
|
|
This permit was created on the web by william kerwin
|