Final | 6/21/2020 | 6/22/2020 | 6/22/2020 | A | PASS |
Jack Reynolds
|
|
|
Garage code is 2022 Phone #: ###-#### Inspection requested via web by Arcadio Martinez - final ok
|
Final | 6/17/2020 | 6/18/2020 | 6/18/2020 | A | FAIL |
Jack Reynolds
|
|
|
Garage code is 2022 Phone #: ###-#### Inspection requested via web by Arcadio Martinez - fresh air duct in garage needs insulated - line set UV protection and penetration needs sealed - A/C locking caps
|
Rough-in | 1/29/2020 | 1/30/2020 | 1/30/2020 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Arcadio Martinez- R/I ok- need fireplace permit issued- check equipment at final not set on R/I
|
Rough-in | 1/27/2020 | 1/28/2020 | 1/28/2020 | P | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Arcadio Martinez 1- need city approved man j onsite -ducting doesnt match man j onsite 2- dryer duct to termination box 2nd floor needs sealed 3- need to seal 20 to 16 supply reducer in chase and all mastic needs to maintain thickness of a nickel all joints crimps can be seen 1st and 2nd floor chases 4- need to fix all rips and tears in arma flex in crawl bare copper showingmultiple place
left notice front window
|
Pressure Test | 1/27/2020 | 1/28/2020 | 1/28/2020 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Arcadio Martinez- 20lb gas pass tagged meter loction- 5lb flue
|
Telephone call | | | 1/28/2020 | | DONE |
|
|
|
Jenifer Jenson called in to removed the fireplace from the scope of work.
|
Issue PAID IN FULL permit | | | 1/24/2020 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 1/24/2020 | | DONE |
|
|
|
This permit was created on the web by Arcadio Martinez
|