Pressure Test | 2/26/2020 | 2/26/2020 | 2/26/2020 | P | PASS |
Ben Livingston
|
|
|
gas line for out door kitchen Phone #: ###-#### Inspection requested via web by Eric Sonner -20lb-
|
Pressure Test | 2/19/2020 | 2/20/2020 | 2/20/2020 | A | FAIL |
Ben Livingston
|
|
|
low pressure gas line for out door kitchen pressure test. Phone #: ###-#### Inspection requested via web by Eric Sonner - piping cannot enter building from below grade - - low pressure test 20lb on 30lb gauge, med pressure test 60lb on a 100lb gauge -
|
Rough-in | 2/11/2020 | 2/12/2020 | 2/12/2020 | A | FAIL |
Ben Livingston
|
|
|
Please call if there are any questions thanks Phone #: ###-#### Inspection requested via web by Eric Sonner - manual J needs tobe submitted for approval to the city - - please put a end cap on gas pipe to future water heater - - supply duct in attic isnt run per manual j , duct in crawl isnt complete-
|
Rough-in | 2/10/2020 | 2/11/2020 | 2/11/2020 | A | FAIL |
Ben Livingston
|
|
|
Phone #: ###-#### Inspection requested via web by Eric Sonner - ducted mini splits need a manual J report - - linesets in attic need more supports -
|
Rough-in | 2/10/2020 | 2/10/2020 | 2/10/2020 | P | PASS |
Eric Strole
|
|
|
Pressure test furnace vent line. Phone #: ###-#### Inspection requested via web by Eric Sonner-Flue tests pass.
|
Rough-in | 2/4/2020 | 2/5/2020 | 2/5/2020 | A | CANC |
Ben Livingston
|
|
|
Rough in Go over project Phone #: ###-#### Inspection requested via web by Eric Sonner - consultation on rough in -
|
Issue PAID IN FULL permit | | | 1/29/2020 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 1/29/2020 | | DONE |
|
|
|
This permit was created on the web by Eric Sonner
|